Locations
Select a location to learn more:
Downtown Los Angeles - LAX 1
- Year Built: 1983 Phase I ; 2009 Phase II
- Building Size: 226,943 square feet (raised floor area)
- Raised Floor Height: 18"
- UPS System: Phase 1 UPS Power Plant Made Up of five (5) Emerson Liebert 750 kVA UPS Models; Net2EZ has own internal Powerware UPS
- Generators: Phase I Emergency Generator Plant with four (4) Detroit Diesel 1,100 kW generators and one (1) Cummins Electric 1,250 kW generator resulting in 5.65 MW; Phase II: Phase II Emergency Generator Plant with five (5) Cummins Electric 2,250 kW generators resulting in 11.25 MW.
- HVAC Chiller Plants: Phase I HVAC Chiller Plant with three (3) Trane 1,000-ton centrifugal chillers and two (2) Trane 500-ton centrifugal chillers resulting in 4,000 ton capacity. Phase II HVAC Chiller Plant is four (4) Trane 1,200-ton centrifugal chillers resulting in 4,800 ton capacity.
- Total Power: 16.9 MW/150W per square foot
- Fire Protection: Laser based Very Early Smoke Detection (VESDA) and a dual action sprinkler system
- Security: Security check-in, front window areas and loading dock ; Staffed 24/7 ; Electronic Security features with card key access; Alarm System; CCTV
El Segundo, Los Angeles - LAX 4
- Year Built: 2000
- Building Area: 135,600 square feet (80,000 usable sq ft floor plate area)
- Access: Keycard/biometric scanner/24x7 Security Staff
- Telecom Type/Capacity: Copper/Fiber
- Flooring: 24" raised, 2'x 2' floor plates
- HVAC: 5 chillers at 670 Tons each; Seven(7) 30-ton CRAC units per data room; 5 cooling towers; 5 chilled water pumps; 3 chillers, giving N+2 redundancy
- Fire Suppression: Dry pipe, pre-action system VESDA and/or early smoke detectors
- Power: EPS/UPS or emergency generator; 100% connected load on 5 Hitches and 2 standby generators. Two 25,000 gallon diesel storage tanks on site; six (6) HiTech CPS continuous and conditioned power generation rotary UPS systems to an N+1 capacity; each room has 800 AMP redundant -48 volt DC battery system. 150 Watts per square foot
Downtown Los Angeles - LAX 6
- Year Built: 1914; Complete structural upgrade to telecom standards in 1999
- Building Area: 67,000 usable sq ft floor plate area
- Access: Keycard/biometric scanner/ video monitoring/recording/24x7 Security Staff
- Telecom Type/Capacity: Fiber/inner ducts
- Flooring: 18" raised, 2'x 2' floor-plates
- HVAC: Condenser water sources (configured as N+1); (11) 30-ton units
- Fire Suppression: Double interlock pre-action system and heat & smoke detection
- Power: Utility power (2500 Amp 480V feed); Generator back-up (4 1500 kW generators, N+1 paralleled); UPS (Six 300 kVA UPS power plants configured as 2N). Circuits available at 120V, 208V single phase
Ashburn, VA - IAD1
- Year Built: 2008
- Building Size: 360,000 raised floor area
- Nearest Airport: 7 miles from Dulles International Airport
- Raised Floor Height: 42"
- UPS System: 32 Rotary power systems with 1300 kW of critical output; N+2 Redundancy
- Generators: 32 diesel-powered emergency generators with 2,250 kW capacity; N+2 Redundancy
- Heat Rejection Systems: Water cooled chilled water cooling system with multiple air handler units, capacity 17,280 Tons; N+3 Redundancy
- Total Power: 36.4 MW/350W per square foot in data center space
- Fire Protection: Laser based Very Early Smoke Detection (VESDA) and a dual action sprinkler system
- Security: Bullet resistant protection at security check-in, front window areas and loading dock ; Staffed 24/7; Electronic Security features with card key access; Alarm System; CCTV
Reston, VA - IAD3
- Year Built: 2001
- Building Size: 256,000 square feet raised floor
- Raised Floor Height: 28"
- UPS System: 13 MW of critical load; rotary power systems with 1300 kW of critical output; N+2 Redundancy
- Generators: 18 Diesel-power emergency generators with 2000 kW capacity each;N+2 Redundancy
- HVAC: (6) 970 ton centrifugal chillers N+2 Redundancy
- Total Power: 13 MW/170W per square foot in data center space
- Fire Protection: Laser based Very Early Smoke Detection (VESDA) and a dual action sprinkler system
- Security: Bullet resistant protection at security check-in, front window areas and loading dock ; Staffed 24/7; Electronic Security features with card key access; Alarm System; CCTV
Ashburn, VA - IAD4
- Year Built: 2009
- Building Size: 176,200 raised floor area
- Nearest Airport: 7 miles from Dulles International Airport
- Raised Floor Height: 42"
- UPS System: 32 Rotary power systems with 1300 kW of critical output; N+2 Redundancy
- Generators: 32 diesel-powered emergency generators with 2,250 kW capacity; N+2 Redundancy
- Heat Rejection Systems: 16 centrifugal chillers with 1,080 Ton capacity each
- Total Power: 36.4 MW/350W per square foot in data center space
- Fire Protection: Laser based Very Early Smoke Detection (VESDA) and a dual action sprinkler system
- Security: Bullet resistant protection at security check-in, front window areas and loading dock ; Staffed 24/7; Electronic Security features with card key access; Alarm System; CCTV
Piscataway NJ (NY Metro) - EWR1
- Year Built: 2010
- Building Size: 176,200 square feet raised floor
- Raised Floor Height: 42"
- UPS System: 32 Rotary power systems with 1,300 kW of critical output each; N+2 Redundancy
- Generators: 32 diesel-powered engine generators with 2,250 kW capacity each;N+2 Redundancy
HVAC 16 centrifugal chillers with 1,080 Ton capacity each
- Total Power: 36 MW/350W per square foot in data center space
- Fire Protection: Laser based Very Early Smoke Detection (VESDA) and a dual action sprinkler system
- Security: Bullet resistant protection at security check-in, front window areas and loading dock ; Staffed 24/7; Electronic Security features with card key access; Alarm System; CCTV
Each net2EZ Managed Data Center is strategically located to access the Internet hub and telecommunications carrier hotels to optimize the network connectivity options available to our customers. With our Managed Network Services, our customers have access to hundreds of networks within a single cross connect. The power density for each collocation cabinet is one of the highest available in the industry, up to 350 watts per square foot or up to 22kW per cabinet. Each market offers unique benefits, and yet collectively they offer our customers highest reliability data center since 2006 with 100% uptime performance.